3015-4190
Bacharach AGM300 Multi-Zone Ammonia Monitor, 4
|
 |
|
AGM300: 4 zones, 120VAC/60Hz Input Power
|
|
Select refrigerants to be measured - point by point
|
|
Eliminate false alarms with use of non-dispersive IR source and sample draw system
|
|
Measure all gases up to 10,000 ppm with a sensitivity of 1 ppm
|
|
Sample points locate up to 500 feet from unit
|
|
Remotely interrogate, acknowledge alarms
|
|
Quick field expansion from 4 to 16 sampling zones
|
|
Bolt-in, bolt-out internal components so the unit never leaves the wall
|
|
Full two-way communication via RS-458
|
|
RS-232 port for local / modem communication
|
|
Split-architecture design keeps your investment to a minimum
|
|
UL and CE approved
|
|
Two-year warranty
|
|
Multiple refrigerant gas and multiple area monitor. May be used "stand alone" or combined with other HGM300 /AGM300 units reporting to the RDM-800 / ADM-800 remote display.
|
|
Refrigerants: R-717 (Ammonia)
|
|
Measuring Range: 25 to 10,000 ppm
|
|
Inputs: 4 points standard, expandable to 16 points in 4 point increments
|
|
Output Signal: 4?20 mA DC (optional)
|
|
Detector Type: Non-dispersive infrared
|
|
Sensitivity: All gases 1 ppm
|
|
Accuracy: All gases ?10 ppm from 0 to 100 ppm, ?10% of reading from 100 to 10,000 ppm
|
|
Front Panel Display: Green LED indicates when unit is operating properly. Red LED indicates when any monitored point is above its alarm setting. Yellow LED indicates a clogged sample line or other system fault.
|
|
Response Time: 5 to 120 seconds, depending on tube length and gas concentration
|
|
Max. Monitoring Distance: Up to 500 feet from measuring point to monitor
|
|
Operating Temperature: 32 to 113 ?F (0 to 45 ?C)
|
|
Power: 120/240 VAC, 50/60 Hz
|
|
Size/Weight: 17" x 12" x 5.5" / 15 lbs (may be wall or rack mounted) |
|
Price: $5238.00
|